Duct Leakage Testing in Hartford, CT

air duct

A duct leakage tester is a diagnostic tool designed to measure the airtightness of forced air heating, ventilating and air-conditioning (HVAC) ductwork. A duct leakage tester consists of a calibrated fan for measuring an air flow rate and a pressure sensing device to measure the pressure created by the fan flow.

The combination of pressure and fan flow measurements is used to determine the ductwork airtightness. The airtightness of ductwork is useful knowledge when trying to improve energy conservation.

These are the various methods for conducting a duct leakage test:

  • Using only a blower door (not recommended)
  • Using a blower door and pressure pan (for diagnostic purposes only)
  • Using a duct leakage tester and blower door together (most common method)
  • Using a flow hood

The basic idea behind using a duct leakage tester:

  • Using a calibrated fan to pressurize the duct system
  • Measuring the airflow through the fan with the duct system at pressure

And when you’re testing for airtightness, each cubic foot of air that leaks out of the duct system must be made up by a cubic foot of air blown in by the fan. So once you’ve measured the amount of air moving through the fan, you’ve quantified the duct leakage at the test pressure.

Contact Us For An Estimate

Fields with (*) are required.
Full Name*
Phone Number*
Email Address*
Comments

Standard Pressure

For duct leakage testing, the standard pressure used is 25 Pascals, which is close to the operating pressure of a typical duct system. This means that when we measure, for example, 120 cubic feet per minute of duct leakage at 25 Pascals (written as 120 cfm25), that number is a pretty good estimate of how much air leaks out of the duct system while operating.

Two Kinds of Leaks

There are two kinds of leaks, benign and malignant. The malignant leaks are the ones that need immediate attention. They’re the ones that send conditioned air into unconditioned spaces, or suck the unconditioned air into the system. Benign leaks are the ones leaking inside the conditioned space; they don’t exact an energy penalty.

These two kinds of duct leakage, of course, require two different types of tests. The malignant leaks occur in ducts that are outside the conditioned space, or outside of the building envelope, in building science jargon, so the most important test is called an “outside leakage test.” The other test is called the “total leakage test.”

If you would like our help in conducting the ideal duct leakage test for your home, we at Climate Partners would be more than happy to assist you. We give you premium service and help you save on cost. If you're in the surrounding areas of Hartford, CT,, don’t hesitate to call 860-325-4143 or visit our contact page.